EQ Credit 8.1

EQ Credit 8.1: Daylight & Views: Daylight 75% of Spaces
1 Point

Intent
Provide for the building occupants a connection between indoor spaces and the outdoors through the introduction
of daylight and views into the regularly occupied areas of the building.

Requirements
OPTION 1 — CALCULATION

Achieve a minimum glazing factor of 2% in a minimum of 75% of all regularly occupied areas. The glazing
factor is calculated as follows:

Glazing Height   =   Window Area [SF]   x  Window Geometry   x     Actual Tvis      x   Window Height
      Factor                  Floor Area [SF]                  Factor                   Minimum Tvis                 Factor

 
OR

OPTION 2 — SIMULATION
Demonstrate, through computer simulation, that a minimum daylight illumination level of 25 footcandles has
been achieved in a minimum of 75% of all regularly occupied areas. Modeling must demonstrate 25 horizontal footcandles under clear sky conditions, at noon, on the equinox, at 30 inches above the floor.

OR

OPTION 3 — MEASUREMENT

Demonstrate, through records of indoor light measurements, that a minimum daylight illumination level of 25 footcandles has been achieved in at least 75% of all regularly occupied areas. Measurements must be taken on a 10-foot grid for all occupied spaces and must be recorded on building floor plans.

In all cases, only the square footage associated with the portions of rooms or spaces meeting the minimum illumination requirements can be applied towards the 75% of total area calculation required to qualify for this credit.

In all cases, provide daylight redirection and/or glare control devices to avoid high-contrast situations that could impede visual tasks. Exceptions for areas where tasks would be hindered by the use of daylight will be considered on their merits.

Potential Technologies & Strategies
Design the building to maximize interior daylighting. Strategies to consider include building orientation, shallow floor plates, increased building perimeter, exterior and interior permanent shading devices, high performance glazing and automatic photocell-based controls. Predict daylight factors via manual calculations or model daylighting strategies with a physical or computer model to assess footcandle levels and daylight factors achieved.