Air Force sheild Sustainability Toolkit
spacer spacer
LEED Guidance

 

spacer
LEED section image
  LEED Guidance
spacer spacer
spacer
EQ Credit 5
EQ Credit 5: Indoor Chemical & Pollutant Source Control
1 Point

Intent
Minimize exposure of building occupants to potentially hazardous particulates and chemical pollutants.

Requirements
Design to minimize and control pollutant entry into buildings and later cross-contamination of regularly occupied
areas:
  • Employ permanent entryway systems at least six feet long in the primary direction of travel to capture dirt
    and particulates from entering the building at all entryways that are directly connected to the outdoors.
    Acceptable entryway systems include permanently installed grates, grilles, or slotted systems that allow for cleaning underneath. Roll-out mats are only acceptable when maintained on a weekly basis by a contracted service organization. Qualifying entryways are those that serve as regular entry points for building users.
  • Where hazardous gases or chemicals may be present or used (including garages, housekeeping/laundry areas and copying/printing rooms), exhaust each space sufficiently to create negative pressure with respect to adjacent spaces with the doors to the room closed. For each of these spaces, provide self-closing doors and deck to deck partitions or a hard lid ceiling. The exhaust rate shall be at least 0.50 cfm/sq.ft., with no air recirculation. The pressure differential with the surrounding spaces shall be at least 5 Pa (0.02 inches of water gauge) on average and 1 Pa (0.004 inches of water) at a minimum when the doors to the rooms are closed.
  • In mechanically ventilated buildings, provide regularly occupied areas of the building with air filtration media prior to occupancy that provides a Minimum Efficiency Reporting Value (MERV) of 13 or better. Filtration should be applied to process both return and outside air that is to be delivered as supply air.
Potential Technologies & Strategies
Design facility cleaning and maintenance areas with isolated exhaust systems for contaminants. Maintain physical isolation from the rest of the regularly occupied areas of the building. Install permanent architectural entryway systems such as grills or grates to prevent occupant-borne contaminants from entering the building. Install highlevel filtration systems in air handling units processing both return air and outside supply air. Ensure that air handling units can accommodate required filter sizes and pressure drops.