EQ Credit 3.2: Construction IAQ Management Plan:
Before Occupancy
1 Point
Intent
Reduce indoor air quality problems resulting from the
construction/renovation process in order to help sustain
the comfort and well-being of construction workers and building
occupants.
Requirements
Develop and implement an Indoor Air Quality (IAQ) Management Plan
for the pre-occupancy phase as follows:OPTION 1 — Flush-Out
- After construction ends, prior to occupancy and with all interior
finishes installed, perform a building flushout
by supplying a total air volume of 14,000 cu.ft. of outdoor air per
sq.ft. of floor area while maintaining
an internal temperature of at least 60 degrees F and relative
humidity no higher than 60%.
OR
- If occupancy is desired prior to completion of the flush-out, the
space may be occupied following delivery
of a minimum of 3,500 cu.ft. of outdoor air per sq.ft. of floor area
to the space. Once a space is occupied, it
shall be ventilated at a minimum rate of 0.30 cfm/sq.ft. of outside
air or the design minimum outside air rate
determined in EQ Prerequisite 1, whichever is greater. During each
day of the flush-out period, ventilation
shall begin a minimum of three hours prior to occupancy and continue
during occupancy. These conditions
shall be maintained until a total of 14,000 cu.ft./sq.ft. of outside
air has been delivered to the space.
OR
OPTION 2 — Air Testing
- The air sample testing shall be conducted as follows:
1) All measurements shall be conducted prior to occupancy, but
during normal occupied hours, and with the
building ventilation system starting at the normal daily start time
and operated at the minimum outside
air flow rate for the occupied mode throughout the duration of the
air testing.
2) The building shall have all interior finishes installed,
including but not limited to millwork, doors, paint,
carpet and acoustic tiles. Non-fixed furnishings such as
workstations and partitions are encouraged, but
not required, to be in place for the testing.
3) The number of sampling locations will vary depending upon the
size of the building and number of ventilation
systems. For each portion of the building served by a separate
ventilation system, the number of
sampling points shall not be less than one per 25,000 sq.ft., or for
each contiguous floor area, whichever
is larger, and include areas with the least ventilation and greatest
presumed source strength.
4) Air samples shall be collected between 3 feet and 6 feet from the
floor to represent the breathing zone of
occupants, and over a minimum 4-hour period.
Potential Technologies & Strategies
Prior to occupancy, perform a building flush-out or test the air
contaminant levels in the building. The flush-out
is often used where occupancy is not required immediately upon
substantial completion of construction. IAQ
testing can minimize schedule impacts but may be more costly.
Coordinate with Indoor Environmental Quality
Credits 3.1 and 5 to determine the appropriate specifications and
schedules for filtration media.
|
|
|