Air Force sheild Sustainability Toolkit
spacer spacer
LEED Guidance

 

spacer
LEED section image
  LEED Guidance
spacer spacer
spacer
EQ Prerequisite 2
EQ Prerequisite 2: Environmental Tobacco Smoke (ETS) Control
Required

Intent
Minimize exposure of building occupants, indoor surfaces, and ventilation air distribution systems to Environmental
Tobacco Smoke (ETS).

Requirements
OPTION 1
  • Prohibit smoking in the building.
  • Locate any exterior designated smoking areas at least 25 feet away from entries, outdoor air intakes and operable
    windows.

OR

OPTION 2

  • Prohibit smoking in the building except in designated smoking areas.
  • Locate any exterior designated smoking areas at least 25 feet away from entries, outdoor air intakes and operable windows.
  • Locate designated smoking rooms to effectively contain, capture and remove ETS from the building. At a minimum, the smoking room must be directly exhausted to the outdoors with no re-circulation of ETS-containing air to the non-smoking area of the building, and enclosed with impermeable deck-to-deck partitions. With the doors to the smoking room closed, operate exhaust sufficient to create a negative pressure with respect to the adjacent spaces of at least an average of 5 Pa (0.02 inches of water gauge) and with a minimum of 1 Pa (0.004 inches of water gauge).
  • Performance of the smoking room differential air pressures shall be verified by conducting 15 minutes of measurement, with a minimum of one measurement every 10 seconds, of the differential pressure in the smoking room with respect to each adjacent area and in each adjacent vertical chase with the doors to the smoking room closed. The testing will be conducted with each space configured for worst case conditions of transport of air from the smoking rooms to adjacent spaces with the smoking rooms’ doors closed to the adjacent spaces.
OR

OPTION 3 (For residential buildings only)
  • Prohibit smoking in all common areas of the building.
  • Locate any exterior designated smoking areas at least 25 feet away from entries, outdoor air intakes and operable windows opening to common areas.
  • Minimize uncontrolled pathways for ETS transfer between individual residential units by sealing penetrations in walls, ceilings and floors in the residential units, and by sealing vertical chases adjacent to the units.
  • All doors in the residential units leading to common hallways shall be weather-stripped to minimize air leakage into the hallway.
  • If the common hallways are pressurized with respect to the residential units then doors in the residential units leading to the common hallways need not be weather-stripped provided that the positive differential pressure is demonstrated as in Option 2 above, considering the residential unit as the smoking room. Acceptable sealing of residential units shall be demonstrated by a blower door test conducted in accordance with ANSI/ ASTM-E779-03, Standard Test Method for Determining Air Leakage Rate By Fan Pressurization, AND use the progressive sampling methodology defined in Chapter 4 (Compliance Through Quality Construction) of the Residential Manual for Compliance with California’s 2001 Energy Efficiency Standards (www.energy. ca.gov/title24/residential_manual). Residential units must demonstrate less than 1.25 square inches leakage area per 100 square feet of enclosure area (i.e. sum of all wall, ceiling and floor areas).
Potential Technologies & Strategies
Prohibit smoking in commercial buildings or effectively control the ventilation air in smoking rooms. For residential
buildings, prohibit smoking in common areas, design building envelope and systems to minimize ETS
transfer among dwelling units.